Specification

  • Refer to Promaseal IBS Table - *If sealant is not used in this application the fire resistance achieved will be -/180/90. For joints up to 30mm wide it is possible to install a 10mm thick PROMASEAL® IBS™ into the joint on the element’s side exposed to fire without a sealant coating.
  • **If sealant is not used in this application the fire resistance achieved will be -/240/180. For joints up to 30mm wide it is possible to install a 12mm thick PROMASEAL® IBS™ from the element’s side unexposed to fire without a sealant coating.
  • The non fire resistant sealant consists of acrylic, silicone or polyurethane based materials. To install PROMASEAL® IBS™, compress and insert into the joints. For gaps up to 30mm, it is possible to install the PROMASEAL® IBS™ in the centre of the depth/thickness of the floor or wall without a sealant fill. The fire reistance achieved depends on the existing fire resistance level of the building element in which the PROMASEAL® IBS™ is installed.
  • Tested to AS1530.4 & AS4072.1
  • Non loadbearing.